1. Sensors, actuators and signal types

Basic★ Must knowLesson 1 of 10

Sensors (inputs):

SensorMeasures / detectsOutput
Inductive proximityMetal object presentDigital (PNP/NPN)
Capacitive proximityAny material (level in tank)Digital
PhotoelectricObject breaks light beamDigital
Limit switchMechanical positionDigital
RTD (PT100) / thermocoupleTemperatureAnalog
Pressure / level / flow transmitterProcess valuesAnalog 4–20 mA, HART, fieldbus
EncoderSpeed / positionPulses (high-speed counter)

Actuators (outputs): contactors and motors, VFD (variable frequency drive — controls AC motor speed), solenoid valves, pneumatic cylinders, control valves, servo drives, indicator lamps, buzzers.

Signal types:

TypeRangeNotes
Digital (discrete)24 V DC on/offPNP (sourcing) vs NPN (sinking) sensors
Analog current4–20 mA4 mA = 0 %, 20 mA = 100 %; < ~3.8 mA means broken wire ("live zero"); immune to voltage drop on long cables
Analog voltage0–10 VSimple, but affected by cable length/noise
PulsekHzFlow meters, encoders

Scaling an analog value: value = (raw − rawMin) / (rawMax − rawMin) × (engMax − engMin) + engMin. Example: a Siemens analog input gives 0–27648 for 4–20 mA; a 0–10 bar transmitter reading 13824 → 5 bar.